Indoor Fixed Type Vacuum Circuit Breaker
Please Write your message, ask for price, we will reply you soon, thanks
Product Overview
The VD4/S indoor fixed type vacuum circuit-breakers are designed for indoor installation in air-insulated switchgear systems, providing reliable protection and control for medium voltage electrical distribution networks.
Key Benefits
- Exceptional switching capacity for normal and fault conditions
- High reliability and extended service life
- Ideal for networks with high switching frequency
- Compatible with various switchgear systems (SM6, Uniswitch, HXGN)
- Suitable for autoreclosing operations
Product Description
General
The vacuum circuit-breakers of type VD4/S are intended for indoor installation in air-insulated switchgear systems. They have a switching capacity capable of handling the loads occurring at start-up and shutdown of equipment and plant units both in normal and in fault state.
Application Range & Installation
Vacuum circuit-breakers have particular advantages for use in networks where there is a high switching frequency in the working current range and/or where a certain number of short-circuit breaking operations are expected. Designed in column form, these breakers can be supplied as individual units for integration with SM6, Uniswitch, HXGN, and other switchgear systems.
Performance Features
Type VD4/S vacuum circuit-breakers are suitable for autoreclosing, and have exceptionally high operating reliability and long life. Their vacuum interrupter technology ensures rapid arc extinction and minimal maintenance requirements, making them ideal for critical electrical distribution applications.
Technical Data
Guideline Values for Function Times
| Operation | Time (ms) | Tolerance |
|---|---|---|
| Opening time | 45 | ±5 |
| Break time | 60 | ±5 |
| Closing time | 70 | ±10 |
Electrical Specifications
| Parameter | Value |
|---|---|
| Rated voltage | 12kV / 24kV / 36kV |
| Rated current | 630A / 1250A / 2000A / 3150A |
| Short-circuit breaking capacity | 16kA / 20kA / 25kA / 31.5kA / 40kA |
| Mechanical endurance | 10,000 – 30,000 operations |
Standards and Specifications
The switchgear complies with the following specifications in accordance with DIN, VDE and the relevant IEC publications:
- VDE0670, part1000 and IEC60694
- VDE0671, part100, and IEC62271-100
- GB1984-2003
Installation and Operation
The relevant specifications are to be taken into account during installation and operation, particularly:
- DIN VDE0101, Power installations exceeding AC1 kV
- VDE0105, Operation of electrical installations
- DIN VDE0141, Earthing systems for special power installations with rated voltages above 1kV
- Accident prevention regulations issued by the appropriate professional bodies or comparable organizations
- Installation and maintenance must be performed by qualified personnel only. Always follow proper safety procedures.
Operating Conditions of Fixed Type Vacuum Circuit Breaker
Normal Operating Conditions
Design to VDE 0670, part 1000, “Common specifications for high-voltage switchgear and controlgear standards” and IEC-60694, with the following limit values:
Ambient Temperature
Maximum +40°C
Maximum 24 hour average +35°C
Minimum (according to “minus 5 indoor class”) –5°C
Humidity
24h average relative humidity: ≤95%
24h average water vapor pressure: ≤2.2 kPa
Monthly average relative humidity: ≤90%
Monthly average water vapor pressure: ≤1.8 kPa
Site Altitude
Maximum site altitude: ≤1000 m above sea level
Special Operating Conditions
Special operating conditions are to be agreed on by the manufacturer and user. The manufacturer must be consulted in advance about each special operating condition:
Site Altitude Over 1000 m
Allow for the reduction in the dielectric strength of the air.
Increased Ambient Temperature
Current carrying capacity is reduced. Provide additional ventilation for heat dissipation.
Climate Considerations
Avoid the risk of corrosion or other damage in areas with high humidity and/or major rapid temperature fluctuations. Implement preventive measures (e.g. electric heaters) to preclude condensation phenomena.
Decoding Transformer Nameplates: Complete Guide to Ratings (kVA, Voltage, Impedance)
Decoding Transformer Nameplates: Complete Guide to Ratings (kVA, Voltage, Impedance) Master the critical information hidden in plain sight on every power transformer nameplate 💡 Engineering Insight from the Field As a senior electrical engineer, I...
Read MorePower Transformer vs. Distribution Transformer: 7 Key Differences
Power Transformer vs. Distribution Transformer: Key Differences and Application Analysis Author: ElecBase Engineering Team | Last Updated: January 2025 Reading Time: 8 minutes | Technical Level: Intermediate to Advanced Table of Contents Introduction: Understanding the...
Read MoreThe Ultimate Guide to Step-Up Power Transformers
The Ultimate Guide to Step-Up Power Transformers The Ultimate Guide to Step-Up Power Transformers Step-up transformers are foundational pillars of modern electrical grids, yet their monumental importance is often overlooked. As the powerful gateways between...
Read MoreStep-Down Transformer 101: The Ultimate Guide to How They Power Your World
Step-Down Transformer 101: The Ultimate Guide to How They Power Your World From the power grid to your wall socket, discover the unsung hero that makes our modern lives possible. This guide covers everything an...
Read MoreWhat Are the Types of SF6 Circuit Breakers?
What Are the Types of SF6 Circuit Breakers? Choosing the right SF6 circuit breaker can be confusing. Making the wrong choice can lead to operational issues or safety risks. Understanding the core classifications simplifies the...
Read More